Combined Fireproof and Stuffing Materials Applied to Through-Floor Pipes
| Periodical | Advanced Materials Research (Volumes 152 - 153) |
|---|---|
| Main Theme | New Materials and Advanced Materials |
| Edited by | Zhengyi Jiang, Jingtao Han and Xianghua Liu |
| Pages | 1547-1550 |
| DOI | 10.4028/www.scientific.net/AMR.152-153.1547 |
| Citation | Shih Feng Kao et al., 2010, Advanced Materials Research, 152-153, 1547 |
| Online since | October, 2010 |
| Authors | Shih Feng Kao, Yu Shiang Wu, Chi Jan Huang |
| Keywords | Combination Method, Fireproof Material, Stuffing Material, Through-Floor Pipe |
| Price | US$ 28,- |
This study tested four types of fireproof and stuffing materials, including firestop sheets, silicone fire barrier sealant, mineral wool batt, and double agent fire barrier foam, on through-floor pipes and walls. Based on the specifications of the American society for testing and materials (ASTM) E84, a 10 min substrate surface burning test was conducted to test fireproof and stuffing materials. The results indicated that the level of fireproof material substrates reached the level of class A in ASTM E84. Combination methods A and B were tested by 180 min heating for specimens, according to the ASTM E814 standard temperature-time (T-t) heating curve, followed by the water spraying test. The results showed that methods A and B have 180 min of fire prevention effects (F rating), and method B can achieve 180 min of heat prevention effects (T rating).