Paper Title:
Model Experimental Study on Stratified Air Distribution with 2D-PIV for High Ceiling Industrial Plant
  Abstract

At present, the research ways of stratified air-conditioning technology mainly have two types, experimental study and numerical simulation. In this paper, a transparent Plexiglas model was designed, of which the size was supposed to be 1/50 of the real scale. PIV technology was innovatively applied into the experiment to measure the air distribution of an industrial plant. Different air supply velocities and different kinds of air supply outlets were taken into account to discuss the influence of them. Results revealed that as the jet velocity increased gradually, the airflow’s stratification effect became more evident. When the aspect ratio changed from 1:2 to 1:8, the diffusion degree in vertical direction increased obviously. In comparison with the rectangular air supply outlet, the circular one had lower decay, longer jet distance and better contractibility. The experimental findings are useful for optimizing the design of air distribution in high ceiling industrial plant.

  Info
Periodical
Advanced Materials Research (Volumes 374-377)
Chapter
Chapter 2: Efficient Architecture Equipment, Ventilation, Air Conditioning and Refrigeration Technology
Edited by
Hui Li, Yan Feng Liu, Ming Guo, Rui Zhang and Jing Du
Pages
610-617
DOI
10.4028/www.scientific.net/AMR.374-377.610
Citation
J. Shen, A. G. Li, Y. J. Zhao, "Model Experimental Study on Stratified Air Distribution with 2D-PIV for High Ceiling Industrial Plant", Advanced Materials Research, Vols. 374-377, pp. 610-617, 2012
Online since
October 2011
Export
Price
$32.00
Share

In order to see related information, you need to Login.

In order to see related information, you need to Login.

Authors: Fu Qiang Guo, Rui Bin Mei, Lei Zhang, Jun Wei Fan, Min Xue Li, Yan Li Tang
Chapter 5: HVAC, Air Conditioning and Refrigeration
Abstract:In order to obtain the thermal comfort work environment, the distribution of temperature and airflow velocity in typical computer room of...
717
Authors: Xu Han, Yong Li, Ying Xin Liu
Chapter 5: HVAC, Air Conditioning and Refrigeration
Abstract:Air purifier was used more and more widely, its placement and characteristics of indoor air have a significant impact on the efficiency of...
1240
Authors: Jiu Chen Ma, Zhi Gang Zhang
Chapter 3: Civil Engineering
Abstract:In this energy saving and environment protection society, as a new kind of air conditioning system, the combined cooling ceiling (CC) and...
1048
Authors: Yi Tang, Jin Feng Wang, Jing Xie, Zheng Zhang, Rui Liu
Chapter 11: Heating, Gas Supply, Ventilation and Air Conditioning Works
Abstract:The sales volume of vertical air conditioner in China mainland has developed rapidly. The researches in the field to the operation of...
2106