  Abstract

The three-phase short-circuit fault of the 500 kV busbar of Waigaoqiao No.2 Power Plant was described, and the fault recorder data was analyzed for short-circuit current. The RMS of short-circuit current decaying fundamental frequency component, DC component and the attenuation time constant was obtained by Fourier transform, extrapolating with the exponential function. Finally, Corresponding suggestions for grid operation and management were also proposed.