Study on Overvoltage and Insulation Coordination of DC Filter for UHVDC Project


Article Preview

Based on the UHVDC project from Hami to Zhengzhou, two typical faults for transient stress calculation of DC filter including ground fault on the DC line and incoming switching surge on the DC line are presented. The simulation steep-fronted models and factors including protective characteristics of arresters, parasitic inductances should be considered for these two faults are introduced. The protective level of arresters are obtained according to the calculated maximum according current of arresters, and the insulation levels of the filter equipment are defined according to the insulation margin. The research can provide technical supports for project construction.



Advanced Materials Research (Volumes 1070-1072)

Edited by:

Danhong Cheng, Qunjie Xu and Weifeng Yao




G. Huang et al., "Study on Overvoltage and Insulation Coordination of DC Filter for UHVDC Project", Advanced Materials Research, Vols. 1070-1072, pp. 989-993, 2015

Online since:

December 2014




* - Corresponding Author

[1] Wanjun Zhao. High voltage DC transmission project technology[M]. Beijing, China: China Electric Power Press, (2009).

[2] Zehong Liu, Liying Gao, Jun Yu . ±800kV HVDC transmission technology research [J]. Power Construction, 2007, 28(10): 17-24.

[3] Yian Tian, Wanrong Zhang, Peng Xing. The design and research of ±800kV HVDC transmission project[J]. High Voltage Apparatus, 2012, 48(10): 73-77.

[4] Dingzhen Nie, Jin Zheng. HVDC converter station Insulation Coordination. High voltage Engineering, 2006, 32(9): 75-79.

[5] DC Transmission Research Group. Zhejiang University Electric Engineering Research Group. DC transmission[M]. Beijing: China Electric Power Press, (1985).

[6] Wei Su, Weimin Ma. AC filter steady state rating in HVDC converter station[J]. High voltage Engineering, 2004, 30(11): 63-64.

[7] Jing Yang. Study on performance of ac filter in ling bao converter station[J]. High voltage Engineering, 2004, 30(11): 60-62.

[8] Weimin Ma, Yanming Cao. Key technical schemes for ±800kV UHVDC project from Xiangjiaba to Shanghai [J]. Power System Technology, 2007, 31(11): 1-5.

[9] Jinzhuang Lu, Jie Zhao. Study on the insulation coordination of Yunnan-Guangdong ±800kV UHVDC transmission system [J]. Southern Power System Technology, 2009, 3(2): 18-22.

[10] Dingzhen Nie, Ming Li. Insulation coordination for converter station of ±800kV UHVDC project from Jinping to Sunan [J]. High voltage Engineering, 2010, 36(1): 92-97.

[11] Xiufu Luo, Hua Yu. The research and simulation of HVDC transmission system double tuned filter parameters [J]. Electric Power Automation Equipment, 2006, 26(10): 25-27.

[12] Guopei Wu, Zhen Ren, Zhuoyao Tang. The research of HVDC transmission system double tuned filter characteristics[J]. Power System Technology, 1999, 23(8): 32-34.