Analysis of Vibration and Noise in Transformer under DC Bias

Article Preview

Abstract:

DC bias would cause the half-wave saturation of transformer, distortion of the exaction current, generation of high harmonic and the vibration and noise increases rapidly, which harm the safe operation of the transformers. In this paper, simulation of magnetic vibration and noise of a 160KVA dry-type transformer with DC bias and modal analysis with the finite element software comsol multiphysics is obtained. The software conduct multi-physical field coupling analysis to electric field, magnetic field, structural stress field and acoustic field, calculate the distribution of the noise and the natural frequency of transformer and propose effective measures to reduce the noise and vibration of transformer with DC bias.