The Energy, Environmental and Economic Benefits Analysis of Ground-Source Heat Pump in Wuhan Region of Summer Condition
Abstract:
To study the actual energy-saving rate of a ground-source heat pump system (GSHP), this article discusses the actual performance coefficient of cooling condition. Compared with the conventional water-cooled chillers and conventional coal-fired boiler, there comes to conclusions that the actual average energy-saving rate is 43.9%, which is lower than the calculated , and the energy saving rate of heating conditions is 11.8% higher than that of cooling conditions. What’s more, we come to conclusion that the actual total load is one-third to two-thirds of the calculated total load, resulting that the actual payback period is 98.6% longer than the calculated payback period.