Comparison of Operational Losses under Rated and Nonlinear Loads for 2 kVA Three-Phase Three Legged Dry Type Power Transformer

Article Preview

Abstract:

This paper produces experimental results comparing operational loss of a power transformer under rated and nonlinear load. A 2kVA three phase three legged dry type power transformer is primarily designed for rated loss; however it is operated with a nonlinear load. Three phase rectifier with variable capacitors is the selected current harmonic source and the distortion at current waveform is controlled by the capacitance values. Initially the operation losses under rated load is measured and then followed with measurement with nonlinear load. At the end of this paper, both type of operation losses is compared and differentiated.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

309-314

Citation:

Online since:

September 2015

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2015 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] Goethe, P. K. & Goethe, W. D., (1999).

Google Scholar

[2] IEEE Recommended Practice for Establishing Liquid-Filled and Dry-Type Power and Distribution Transformer Capability When Supplying Nonsinusoidal Load Currents - Redline. IEEE Std C57. 110-2008 (Revision of IEEE Std C57. 110-1998) - Redline.

DOI: 10.1109/ieeestd.2008.4601586

Google Scholar

[3] Driesen, J., Belmans, R. & Hameyer, K., (2000).

Google Scholar

[4] Noda, T., Nakamoto, H. & Yokoyama, S., (2002) Accurate modeling of core-type distribution transformers for electromagnetic transient studies. Power Delivery, IEEE Transactions on, 17, 969-976.

DOI: 10.1109/tpwrd.2002.803700

Google Scholar

[5] Hwang, M. S., Grady, W. M. & Sanders, H. W., (1987) Distribution Transformer Winding Losses Due to Nonsinusoidal Currents. Power Engineering Review, IEEE, PER-7, 46-46.

DOI: 10.1109/mper.1987.5527312

Google Scholar

[6] Rama Rao, D. K. S., (2003).

Google Scholar

[7] Jr, L. H. D. (1988) Eddy Current Losses in Transformer Windings and Circuit Wiring. Unitrode Seminar Manual SEM600.

Google Scholar

[8] Pierce, L. W., (1996) Transformer design and application considerations for nonsinusoidal load currents. Industry Applications, IEEE Transactions on, 32, 633-645.

DOI: 10.1109/28.502176

Google Scholar

[9] Delaiba, A. C., de Oliveira, J. C., Vilaca, A. L. A. & Cardoso, J. R., (1995).

Google Scholar

[10] INTERNATIONAL. STANDARD. IEC. 60076-11.

Google Scholar

[11] Taci, M. S. & Sarul, M. H., (2008) Investigation of a sinusoidaly supplied transformer under linear and non-linear loading conditions. In: TENCON 2008 - 2008 IEEE Region 10 Conference, 19-21 Nov. 2008, 1-6.

DOI: 10.1109/tencon.2008.4766464

Google Scholar

[12] Klontz, K. W., (1995).

Google Scholar

[13] Ahmed, E., Xu, W. & Liu, X., (2001) Application of modal transformations for power system harmonic impedance measurement. International Journal of Electrical Power & Energy Systems, 23, 147-154.

DOI: 10.1016/s0142-0615(00)00041-7

Google Scholar

[14] S. Masri & P.W. Chan, (2011) Determination of Transformer Rating Based on Total Harmonic Distortion Under Balanced Conditions. Journal of Engineering Science, 7, 51-61.

Google Scholar

[15] Daut, I., Hasan, S., Taib, S., Chan, R. & Irwanto, M., (2010) Harmonic content as the indicator of transformer core saturation. In: Power Engineering and Optimization Conference (PEOCO), 2010 4th International, 23-24 June 2010, 382-385.

DOI: 10.1109/peoco.2010.5559192

Google Scholar

[16] Tran-Quoc, T. & Pierrat, L., (1997) Correction of the measured core losses under distorted flux [power transformers]. Magnetics, IEEE Transactions on, 33, 2045-(2048).

DOI: 10.1109/20.582714

Google Scholar

[17] Emanuel, A. E. & Xiaoming, W., (1985) Estimation of Loss of Life of Power Transformers Supplying Nonlinear Loads. Power Apparatus and Systems, IEEE Transactions on, PAS-104, 628-636.

DOI: 10.1109/tpas.1985.318998

Google Scholar

[18] Delaiba, A. C., de Oliveira, J. C., Vilaca, A. L. A. & Cardoso, J. R., (1995).

Google Scholar

[19] Barnes, P. R., Dyke, J. W. V., McConnell, B. W. & S. Das, (1996) Determination Analysis of Energy Conservation Standards for Distribution Transformers. p. ORNL-6847.

DOI: 10.2172/405744

Google Scholar

[20] Temperature Rise, (1998) Application Note. Controlled Power Company.

Google Scholar

[21] Sanjay A. Deokar, L. M. Waghmare, Analysis of Impact of harmonics on power system devices in distribution system and its remedial measures, " Proc. of Elsevier, Energy Procedia, Nov-Dec. 2011, 2nd International conference on , Advances in Energy Engineering (ICAEE-2011).

DOI: 10.1109/icectech.2011.5941817

Google Scholar

[22] INTERNATIONAL STANDARD IEC/EN 61558-1-2.

Google Scholar