The Protection System Design of Leakage, Undervoltage and Overvoltage for Electromagnetic Starter in Coal Mine
Abstract:
For the problem of leakage, undervoltage and overvoltage fault protection of electromagnetic starter with supply voltage of 660 V and rated current of 200A, a leakage, undervoltage and overvoltage protective system based on PLC LM3108K was designed. This system uses voltage transformer to detect three-phase AC voltage. It protects undervoltage and overvoltage fault by judging effective value of three-phase voltage, protects leakage fault of main switch for electromagnetic starter by additional DC power and protects leakage fault of branch switch by using zero-sequence power direction. This system has good protection functions for leakage, overvoltage and undervoltage faults of electromagnetic starter in coal mine.
Info:
Periodical:
Pages:
720-725
Citation:
Online since:
October 2014