The Theoretical and Experimental Researches on a Kind of Dew Point Indirect Evaporative Cooler

Article Preview

Abstract:

This paper designs a novel dew point indirect evaporative cooler. An experimental system of dew point indirect evaporative cooler is built up, The experimental results indicate that temperature of the primary air and the dew point efficiency have a positive relationship with the inlet temperature and relative humidity. Generally, in order to meet the blowing air requirements, maintain the high cooling efficiency and low temperature of the outlet air, the velocity of primary air should be 3m / s and the rate of primary and secondary air should be 1.5:1. When the flux of water is 3L/min the dew point efficiency is highest. In addition, the cooling effect was less affected by the temperature of the water.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 550-553)

Pages:

2685-2689

Citation:

Online since:

July 2012

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2012 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] Maisotsenko,China.Patent 02,828,060.(2002),in Chinese

Google Scholar

[2] J • A • M • Rhine Sanders, E • J • E • Bell Man ,China.Patent 03,814,728.(2003),in Chinese

Google Scholar

[3] W • Major,China .Patent,200680044438.3(2006),in Chinese

Google Scholar

[4] Junping Chen, The optimization and application of Dew point indirect evaporative cooler,Master thesis of Xi'an University of Engineering. 2008:8~26,in Chinese

Google Scholar

[5] Yijun Yuan ,China.Patent 200310122817.8(2003) ,in Chinese

Google Scholar