Calculation and Experiment Research of Improving Generated Energy in Grid-Connected PV Power Station Based on Manual Adjustment of Angle

Article Preview

Abstract:

The method that dividing a year into multiple time periods and calculating the optimum tilt angle of PV panels in every period is proposed. Calculation software is developed using Labview language. Taking some region in Liaoning province for example, the yearly radiation under fixed inclination, two inclinations and three inclinations every year are compared. The capital investment and increased revenue in the case of fixed inclination, adjusting the bracket twice a year and adjusting the bracket three times a year are compared. The calculation results show that adjusting the angle twice a year and adjusting it three times a year can increase the overall yield 4.03% and 4.39% respectively. The test platform is built up. And the experiment results show that the generating capacity of the 8th unit after angle adjustment increases significantly comparing with that of the 5th unit under fixed inclination.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 608-609)

Pages:

17-21

Citation:

Online since:

December 2012

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2013 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] Z.M. Zhao, in:Solar Photovoltaic Power Generation and Its Application, edtied by Science Press, Beijing,(2005), in press.(In Chinese)

Google Scholar

[2] Abdallah s:Energy Conversion and Management. Vol.45(2004), p.1671.

Google Scholar

[3] Kh S Karimov, Saqib M A and Akhter P:Solar Energy Material and Solar Cells. Vol.87(2005), p.49.

Google Scholar

[4] Alata M, Al Nimr M A and Qaroush Y:Energy Conversion and Management. Vol.46(2005), p.1229.

Google Scholar

[5] Q.X. Zhang, H.Y.Yu:Journal of Agricultural Mechanization Research. Vol.10(2010), p.241. (In Chinese)

Google Scholar