Abstract:

In the paper, changes of both outlet temperature and relative humidity of solar powered two-stage wheel desiccant air conditioning system are tested with time under the typical Tianjin summer condition. It is found that supply air temperature of the solar driven desiccant cooling system could steady below 21 degrees Celsius, and the relative humidity of it is more than sixty percent in most of time of the actual operation. When operating, the thermal coefficient of performance of the whole air conditioning unit is about 0.5, and the reliability of two-stage wheel desiccant air conditioning system is verified.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 732-733)

Pages:

609-614

Citation:

Online since:

August 2013

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2013 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] R.Z. Wang, Y.J. Dai. Solar Cooling [M]. Beijing: Chemical Industry Press, (2007)

Google Scholar

[2] Ge T S, Li Y, Wang R Z, Dai Y J. Experimental study on a two-stage rotary desiccant cooling system. International Journal of Refrigeration, 2009, 32(3):498-508

DOI: 10.1016/j.ijrefrig.2008.07.001

Google Scholar

[3] T.H. Zou, R. Yu, L. Yan and F.L. Cao. Experimental study on a solar powered two-stage solid wheel desiccant air conditioning system [J]. Advanced Materials Research, 2012, 1111-1116

DOI: 10.4028/www.scientific.net/amr.516-517.1111

Google Scholar

[4] D.H. Xue. Air-condition [M] Beijing: Tsinghua University Press, (1991)

Google Scholar