The Effect of Dust Overload on Security of Single Layer Steel Structural Workshop

Article Preview

Abstract:

Based on the investigation of a single layer steel structure industry workshop in Baoshan Steel Incorporated Company, the effect of dust overload on the security of single layer steel structural workshop is analyzed, which is the basis of maintenance and monitor of the building. The results show that the dust-load overload 16%, the ratio of resistance-load of roof truss, bracket and framework column separately reduce 4%,4%,0.5%. If the dust-load overload 100%, the ratio of resistance-load of roof truss, bracket and framework column separately reduce 20%, 20%,1%.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 926-930)

Pages:

677-680

Citation:

Online since:

May 2014

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2014 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] Report of reliability of Baosteel Lian steel slag processing plant. Xi'an University of architect and Technology, (2000).

Google Scholar

[2] Steel structure design specifications(2003), National Standard GB50017-2003 of China.

Google Scholar