Effect of Phase Sequence Layout on Electric Field under Overhead Lines

Article Preview

Abstract:

This paper discusses effect of phase sequence layout on electric field under overhead lines. Charge simulation method is used. Examples of two circuit overhead lines and four circuit overhead lines show that phase arrangment of lowest height conductors has major influence and phase arrangment of middle height conductors has lesser influence on electric field under overhead lines. Interlacing placed lowest height conductors with different phase and phase arrangement of middle height conductors different from that of lowest height conductors help to reduce electric field.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 960-961)

Pages:

921-924

Citation:

Online since:

June 2014

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2014 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] Olsen R.G. and Wong P.S.: IEEE Trans. on PD, Vol. 7, No. 4 (1992), p. (2046).

Google Scholar

[2] A.E. Tzinevrakis, D.K. Tsanakas and E.I. Mimos: IET Gener. Transm. Distrib., Vol. 3, iss. 6 (2009), p.509.

Google Scholar

[3] Tadasu Takuma, Tadashi Kawamoto, Mitsuru Yasui, et al: IEEE Trans. on PAS, vol. 104, no. 9 (1985), p.2612.

Google Scholar