Research on a New Fault Phase Selector of Protective Relay for Double Circuit Lines on same Tower
Abstract:
Aiming at the misoperation of the conventional phase selector by phase current-difference during some cross country faults, a fault phase selector is developed. Based on the fault lines of the corresponding fault phase are selected, a novel synthesis fault phase selector using voltages and currents in single circuit at single side is proposed, which is based on comparing the difference of fault voltages to make sure all the fault phase in the lines and judging the phase degree and amplitude condition of the fault currents. Used this scheme and the phase current difference, the fault phase may be picked up correctly in double circuit lines on the same tower, especially in cross country faults.