Research on Low Voltage Ride through of Coal-Fired Power Unit Auxiliary in Henan

Article Preview

Abstract:

The electric power short circuit breakdown may cause low voltage blocking of frequency-converter giving rise to power unit shutdown accident,three typical coal-fired power units are selected to emulate calculations on low voltage ride ability with considering threephase short-circuit earthing fault, threephase short-circuit earthing fault by impedance, single-phase short-circuit earthing fault ,indicating that the short-circuit fault of the lines integrating into power system would result in the voltage of house-service busbar dropping off to 25%-85%,especially threephase short-circuit earthing fault in small operation mode attacks on power unit auxiliary at the most, therefore auxiliary demands complete and dependable low voltage ride through ability. and puts forward to some reform suggestes.