Abstract:

To improve the power quality of power grid in coal mine, a kind of detection and control method for unified power quality controller (UPQC) without phase locked loop (PLL) is put forward. It can get the positive-sequence component of unity fundamental voltage through Park transformation,and then obtains the positive-sequence active component of fundamental current after proper operation . The PLL or filtering of three-phase voltage and the synchronous coordinates transformation for current are cancelled. The control strategy of the system is studied and the effectiveness and validity of UPQC are verified by simulation results.