Application of a New Smith Fuzzy PID in Electric Boiler Temperature Control System

Article Preview

Abstract:

Since the object model is time-varying and time-delay in the electric boiler temperature control system, Smith Fuzzy PID controller is applied in it. Simulation results in the paper show that the overshoot is reduced by 31.3% compared with the system under Smith PID control and the adjusting time reached a 30% reduction compared with those under Fuzzy PID control with T=380 and τ=110. In order to eliminate the oscillation problem in system when model parameters change, a new Smith Fuzzy PID controller with two degrees of freedom is applied, whose control performance is much better than that of Smith Fuzzy PID.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

633-636

Citation:

Online since:

January 2015

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2015 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] WANG Yu-ying, ZHOU Xing-she. Fuzzy-Smith control for Qos-adaptive notification service. Lecture Notes in computer Science, 2007. 46(11): 1140-1147.

DOI: 10.1007/978-3-540-73549-6_111

Google Scholar

[2] KAYA I. IMC based automatic tuning method for PID controllers in a Smith predictor configuration. Computers and ChemicalEngineering, 2004, 28(3): 281−290.

DOI: 10.1016/j.compchemeng.2003.01.001

Google Scholar

[3] GEORGE K I M., HU B G, RAYMOND G G. Analysis of direct action fuzzy PID controller structures. IEEE Trans Syst, Man, Cybern B, 1999, 29(3): 371−388.

DOI: 10.1109/3477.764871

Google Scholar

[4] RAO A S, CHIDAMBARAM M. Analytical design of modified smith predictor in a two-degrees-of-freedom control scheme for second order unstable processes with time delay. ISA Transactions, 2008, 47: 407−419.

DOI: 10.1016/j.isatra.2008.06.005

Google Scholar