Reactive Power Compensation in Oman 400kV Transmission System

Article Preview

Abstract:

The objective of this paper is to present the challenges, methodological approach and possible solutions for the overvoltage issue during the winter light load period in the Main Interconnected Transmission System (MITS) of Oman after introducing the new 400kV system. Load flow studies of the planned MITS in 2016, including representation of other local and GCC interconnection grids, have shown overvoltage issues at the 400kV substations in Oman during winter off-peak demand. These voltage issues can even lead to difficulties in synchronizing the 400kV circuits. Simulation results are presented to define the size and location of a reactive power compensator which can resolve such overvoltage issues. Many options of the reactive power compensation, including fixed and variable means, have been studied and the best option (fixed shunt reactors) is selected.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

455-459

Citation:

Online since:

August 2015

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2015 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] Information on http: /www. omangrid. com.

Google Scholar

[2] OETC and Elecrtricite de France: Reactive Power Compensation Requirements for OETC with 400 kV System 2016, (June, 2013).

Google Scholar

[3] Information on http: /www. digsilent. de.

Google Scholar

[4] A.G. Al-Busaidi and I. French: Modeling of Petroleum Development Oman (PDO) and Oman Electricity Transmission Company (OETC) Power Systems for Automatic Generation Control Studies, Proc. of the ICCP, Sultan Qaboos University, (2009).

DOI: 10.24084/repqj19.333

Google Scholar

[5] O.H. Abdalla, R. Al-Badwawi, H.S. Al-Hadi, and H.A. Al-Riyami: Performance of Oman Transmission System with the 400kV Gulf Cooperation Council Electricity Interconnection, (Proc. IEEE-GCC Conference and Exhibition, Dubai, UAE, pp.601-604.

DOI: 10.1109/ieeegcc.2011.5752599

Google Scholar

[6] W.E. Reid, R.F. Gustin, and P.V. Zylstra: Guidelines for Determining Parallel Resonance on EHV Transmission Lines, (IEEE Trans. on Power Apparatus and Systems, Vol. PAS-102, No. 9, pp.3196-3204, Sept. 1983).

DOI: 10.1109/tpas.1983.318129

Google Scholar

[7] F. Iliceto, E. Cinieri, and A. Di Vita: Overvoltage Due to Open-Phase Occurance in Reactor Compensated EHV Lines, (IEEE Trans. on Power Apparatus and Systems, Vol. PAS-103, No. 3, pp.474-482, March 1984).

DOI: 10.1109/tpas.1984.318725

Google Scholar