Comparison between Parameter of Single Core Unarmoured Aluminium Conductor 6.35/11 kV Underground Cable for Partial Discharge Measurement Using EMTP-ATP Software
Abstract:
Partial Discharge (PD) is one of a symptom in the underground cable before the fault happens.This paper concerned with estimation and detection problems related to PD phenomena in buried underground cables. The Rogowski coil has been implemented to analyze this symptom. The various sizes of nominal cross-sectional area cross-linked polyethylene (XLPE) cable with 6.35/11 KV single core unarmored aluminum conductors that follows Nexans manufacturer datasheet based on design standard IEC 60502 has been used in the simulation using Electromagnetic Transient Program-Alternative Transient Program (EMTP-ATP) software. The Lumped parameter is used for the Rogowski coil sensor model. Meanwhile, for Double-end measurement using J-Marti model is designed to evaluate the parameter changing in the measurement.Based on the measurement, the value of amplitude voltage and current is proportional increase depends on the size of cross-sectional area of conductor XLPE cable.