Thermal Comfort Study of Wall Hanging Air-Conditioning Office in Summer

Article Preview

Abstract:

Airpak was applied to numerically simulate the air distribution under the same air supply temperature ,different air supply velocity (3.6m/s、2.7m/s and 1.8m/s ) and air supply angle (+15°、-45° and-75°) , and evaluate thermal comfort by Comparative analysis velocity fields, temperature fields, PMV—PPD. The results show that different air supply velocity and air supply angle have a significant impact on indoor air distribution under the same air supply temperature. Air supply angle Plays a vital role in pattern and distribution of indoor flow field,air supply velocity mainly effect the magnitude of indoor velocity and temperature. Synthetically comparied, the model’s best supply parameters are supply velocity 2.7m/s and supply angle75°,which mean value of indoor PMV is-0.09, PPD is 8.5%.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 1008-1009)

Pages:

1088-1091

Citation:

Online since:

August 2014

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2014 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] Nielsen P V. Flow in air conditioning rooms [D]. Co-penhagen: Technical University of Denmark, (1974).

Google Scholar

[2] M. Bojic, F. Yik, T.Y. Lo. Locating Air-conditioners and Furniture inside Residential Flats to Obtain Good Thermal Comfort [J]. Energy and Buildings, 2002, 34: 745-751.

DOI: 10.1016/s0378-7788(01)00143-8

Google Scholar

[3] Yonghui Guo, Chao Liu. In Chinese:Numerical simulation of the air flow in a room with low-temperature air distribution[J]. Refrigeration and Air –Conditioning, 2006, 6(5): 35-39.

Google Scholar

[4] Pingfang Hu, Fen Cai. In Chinese:Numerical Simulation on Effects of air distribution to indoor air environment [J]. Journal of Huazhong University of science and technology, 2006, 23(2): 28-31.

Google Scholar

[5] Dongsheng Yuan, Huiling Tian, Jiancheng Gao. In Chinese: Numerical Simulation to the Effect of Airflow Distribution on Air Environment of Air- conditioning Room[J]. Heating Ventilation & Equipment, 2008, 36(211):9-13.

Google Scholar

[6] Qingyan Chen, Weiran Xu. A zero-equation turbulence model for indoor airflow simulation [J]. Energy and Building, 1998, 28: 137-144.

DOI: 10.1016/s0378-7788(98)00020-6

Google Scholar

[7] ISO7730:Moderate thermal environments- Determination of the PMV and PPD indices and specification of the conditions for thermal comfort[S]. (1994).

DOI: 10.3403/00814151

Google Scholar