The Research and Establishment of GIS Fault Simulation Test System

Article Preview

Abstract:

Abstract. In order to accurately analyze the field test results of the partial discharge in GIS and study on the partial discharge characteristics of typical insulation defects in GIS, this paper constructs a set of failure simulation test system which is based on the entity 363kV GIS which contains all the Main equipments. These system has artificial defect setting units and can applied voltage and current at the same time, it also can manually set a variety of GIS typical insulation defects at the defect setting units. The partial discharge detection and analysis in the case of the applied voltage and current can simulate actual field operating conditions of GIS.