10kV Grid Arc Grounding Over-Voltage Hazards and Countermeasures

Article Preview

Abstract:

Through the analysis of 2 single-phase grounding over voltage accidents caused by capacitive over current in 10 kV power grid in this paper, the causes and damages of arc grounding over voltage are illustrated, and the necessity of capacitive current test and effective methods are pointed out. The test and assessment to the 29 substations capacitor currents provides a scientific basis for the correct selection of the neutral point operation mode, and the strengths and weaknesses of the neutral Point grounding through the arc suppression circle and the mode trends of 10kV grid neutral grounding are demonstrated.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

489-493

Citation:

Online since:

September 2013

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2013 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] Xie Guangrun. Over voltage and protection. Power Industry Press, (1980).

Google Scholar

[2] Liu Runlai. The test book for national thermal electric generation . China Power Press, (1998).

Google Scholar

[3] Ping Shaoxun. Power system inner over voltage proection and instance analysis. China Power Press, (2006).

Google Scholar

[4] Yao Huannian, Cao Meiyue. Resonant earthed system[M]. Beijing: China Electric Power Press, (2000).

Google Scholar

[5] Zhang Lisheng. High voltage shunt capacitor operation and maintenance technology. China Power Press, (2008).

Google Scholar

[6] DL/T620-1997 Setting guide for the AC electric setting matching about over voltage and insulation[S]. (1997).

Google Scholar

[7] Xu Ying, Xu Shixian. AC power system over voltage proection and insulation coordination. China Power Press, (2006).

Google Scholar

[8] Yao Huannian, Cao Meiyue. On neutral grounding modes of cable network[J]. Power System Technology, 2003, 27(2): 84-89.

Google Scholar