Calculation of Lighting-Induced Overvoltage on Transmission Line Based on Simplified Wagner Field Cancellation Method

Article Preview

Abstract:

Based on Wagner field cancellation method, the paper presents a simplified method to calculate the induced overvoltage on transmission lines excited by lightning striking on tower. Firstly the square-wave response of lightning-induced voltage is calculated, and then the responses produced by other excitations can be calculated by Duhamel integral. This method can reflect the time-varying characteristic of the induced overvoltage. The simulation results show that the amplitude of lightning current and the length of upward leader have greater impacts on the induced overvoltage.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

1951-1954

Citation:

Online since:

October 2013

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2014 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] Lu Xiaohua. Research of calculation and prevention of lightning induced overvoltages on overhead distribution lines [D]. Hehai University, 2007 ( in Chinese ).

Google Scholar

[2] Nucci C A,Rachidi F,Ianoz M V. Lighming-induced volages on overhead lines[J].IEEE Trans. on E1ectmmagnetic Compatibility, 1993, 35(1): 75—86.

DOI: 10.1109/15.249398

Google Scholar

[3] C.F. Wagner A.R. Hileman. A new approach to calculation of lightning performance of transmission lines-Ⅲ[J]. AIEE. PartⅢ, October 1960: 589-603.

Google Scholar

[4] Yan Fei. Research on the induced overvoltages in electric transmission lines by directly lightning striking on tower[D]. Huazhong University of Science&Technology, 2006 ( in Chinese ).

Google Scholar