Frequency Analysis of the Motor Control Centers in a Nuclear Power Plant Using Testing and Simulating Methods

Article Preview

Abstract:

This study is aim to evaluate the seismic response of the motor control center cabinet in a nuclear power plant using shaking table test and 3D finite element analysis method. Three typical types of motor control center cabinet were used in this study and frequency curves and spectral response acceleration were used as the indices of the dynamic response. The results indicated that the resonance frequency for X and Y direction is about 12 Hz and 15 Hz, respectively, which is verified by the numerical results. The frequencies curves and spectral response acceleration generated by numerical and experimental method were similar and well fitting. Although the numerical method obtained the conservative results, the model accurately represents the dynamic characteristics of the actual motor control center cabinet for seismic verification.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

1045-1050

Citation:

Online since:

December 2013

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2014 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] IEEE Power Engineering. IEEE Std 344-2004, IEEE Recommended Practices for Seismic Qualification of Class 1E Equipment for Nuclear Power Generating Station, Substations Committee, The Institute of Electrical and Electronics Engineers Inc., New York, USA (2005).

DOI: 10.1109/ieeestd.1975.6634497

Google Scholar

[2] S.G. Cho, D. Kim, S. Chaudhary: Nuc. Eng. Des. Vol. 241 (2011), p.2750.

Google Scholar

[3] M.K. Kim, I.K. Choi: A failure mode evaluation of a 480V MCC in nuclear power plants at the seismic events. In: Transactions of the 20th International Conference on Structural Mechanics in Reactor Technology, Espoo, Finland, (2009).

Google Scholar

[4] W. Sur: Nuc. Eng. Technol. Vol. 43 (2011), p.355.

Google Scholar

[5] A.S. Pisharady, P.C. Basu: Nuc. Eng. Des. Vol. 240 (2010), p.3878.

Google Scholar

[6] B.Y. Lee, W.J. Kim, J.Y. Shon, H.M. Shin, S. Kwon, S.H. Kim, S.B. Lee: Dynamic analysis of a cabinet of a reactor protection system. P. I. Mech. Eng. C-J. Mec. Vol. 221 (2007), p.1047.

Google Scholar

[7] IEEE Power Engineering. IEEE Std 693-2005, IEEE Recommended Practices for Seismic Design of Substations, Substations Committee, The Institute of Electrical and Electronics Engineers Inc., New York, USA (2006).

DOI: 10.1109/ieeestd.1984.82450

Google Scholar