Monitoring the Travel Characteristics of High Voltage Circuit Breaker Based on TLD
Abstract:
For the circuit breaker, mechanical fault make up the largest share of the fault. In order to ensure reliable and secure power system can run,it is necessary to monitor the mechanical properties of the circuit breaker,which includes monitoring the breaker trip.By TLD video tracking technology ZN65-12 vacuum circuit breaker mechanical properties were measured,obtain a two-dimensional direction of travel, speed characteristic curves.The experimental results show that the error of the method used to obtain a circuit breaker stroke, speed and other parameters of not more than 1mm,compared with traditional methods of measurement can get richer information.
Info:
Periodical:
Pages:
938-941
Citation:
Online since:
November 2014
Authors:
Keywords:
Price:
Сopyright:
© 2014 Trans Tech Publications Ltd. All Rights Reserved
Share:
Citation: