[3]
inverter parameters configuration The system take the semi-closed loop control mode according to the control demand, so the inverter parameters configuration contains two parts. One is the communication configuration setting, another is closed loop control PID parameters setting. Communication parameters Parameters codes
Value
Instructions
918
1~14
Inverter port's address
916
Sub index1 518
Pcd3 Inverter output frequency
Sub index2 524
PCD4 Motor voltage
Sub index3 520
PCD5 Motor current
Sub index4 517
PCD6 feedback
903
PPO 4
Communicate format
Closed loop control parameters Parameters codes
Value
Instructions
100
1
Speed closed loop
102、103、104、105、106
Set as the motor nameplate
307
29
Pulse feed back
414
0
Min value
415
1350
Rated rotary speed
416
RPM
Set the rotary speed unit
203
0
Same to 414
204
1350
Same to 415
The parameters above are needed by the basic functions of the line. The other parameters, such as PID proportional coefficient, integration time, could be adjusted according to the actual circumstance, please take the VLT2800 inverter work book for more instructions.