New Inverter Fault Current Limiting Method by Considering Microgrid Control Strategy
Abstract:
In this paper we present an approach for fault current limiting (FCL) in inverters of a Microgrid. For this purpose, which is based on the control system employed in Microgrid, we select the proper FCL technique. In this research it is represented that FCL inverter current with limited magnitude of id and iq that are used in PQ control don’t have a good behavior in V-F controlled DG. Current limiting by decreasing the output voltage of DG is performed by the value of inverter reduction of the voltage that is selected by paying attention to the maximum current that is allowed through inverter, this value is two times of the rated current of inverter
Info:
Periodical:
Pages:
1647-1653
Citation:
Online since:
February 2012
Authors:
Price:
Сopyright:
© 2012 Trans Tech Publications Ltd. All Rights Reserved
Share:
Citation: