A Novel Overhead Ground Wire with Winded Insulated Conductors for Ice-Melting
Abstract:
Serious icing on overhead ground wires threatens the safe running of power system. Common overhead ground wires are difficult to realize ice-melting. A novel overhead ground wire structure for ice-melting is proposed. Some conductors coated with insulation layer are winded around the galvanized steel wires in a special way. Ice-melting experiments are performed on the novel overhead ground wire. Experimental results show that 30 W per meter of the wire is an economic power while 40 W per meter of the wire is an effective power for ice-melting. Engineering application of the novel overhead ground wire with insulated conductors is carried out. With the light moveable de-icer, onsite experiment is performed. Under the power of 40 W per meter of the wire, a temperature rise of 10 °C is achieved in 30 minutes. The result shows that the novel overhead ground wire can meet the demands of engineering application.