Research on Harmonic Current Amplification of Parallel Capacitors in a 6kV Substation
Abstract:
This paper investigated the cause of the harmonic current amplification in nonlinear load in a 6kV substations power supply system. The paper proposed that reactors could be series connected in the capacitors by-pass to restrain the amplification. The result from field practice showed that this method could overcome the harmonic current amplification efficiently.
Info:
Periodical:
Pages:
112-115
Citation:
Online since:
July 2013
Authors:
Price:
Сopyright:
© 2013 Trans Tech Publications Ltd. All Rights Reserved