Study on Asynchronous Sampling in Digital Electrical Energy Metering Based on IEC61850

Article Preview

Abstract:

Technical issues regarding asynchronous sampling for digital electrical energy metering based on IEC 61850 are studied. Asynchronous sampling is inevitable when the power network frequency fluctuates. The additional metering error caused by asynchronous sampling is simulated and discussed. The additional error can be as big as 2% under typical conditions, which is unacceptable. Quasi-synchronous sampling algorithm is employed to reduce the error. Simulation result shows that it can reduce the error to an ignorable level. The error under extreme conditions is also simulated and discussed.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 860-863)

Pages:

2417-2422

Citation:

Online since:

December 2013

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2014 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

* - Corresponding Author

[1] IEC 61850(2003): Communication networks and systems in substations.

Google Scholar

[2] IEC 60044-8(2002): Instrument transformers – Part 8: Electronic current transformers.

Google Scholar

[3] IEC 62053-22(2003): Electricity metering equipment (a. c. ) – Particular requirements—Part 22: Static meters for active energy (Class 0. 2S and 0. 5S).

DOI: 10.3403/30350328

Google Scholar

[4] X. Dai: Chinese J. of Sci. instrum., vol. 5 (1984), pp.390-396. (In Chinese).

Google Scholar

[5] X. Dai: Chinese J. of Sci. instrum., vol. 7 (1986), pp.203-207. (In Chinese).

Google Scholar

[6] X. Dai, R. Gretsch: IEEE Trans. On Instrum. and Meas., vol. 42 (1994), pp.204-209.

Google Scholar

[7] X. Dai, T. Tang, R. Gretsch: IEEE IMTC/93, California USA (1993), pp.88-98.

Google Scholar

[8] X. Dai, T. Tang: Proc. of 3rd ICHPS Purdue univ. USA (1988), pp.88-93.

Google Scholar