Research on the Application of Alternative Refrigerants R407C and R410A in Refrigeration-Type Compressed-Air Dryers
Abstract:
The coefficient of performance (COP), the volumetric refrigeration capacity and the pressure ratio of refrigeration cycle were studied in a refrigeration-type compressed-air dryer using environmentally friendly refrigerants R410A and R407C and compared with those using R22. Study indicates that under the working condition of a refrigeration-type compressed-air dryer, COP using R410A is 3% higher than that using R407C, the volumetric refrigeration capacity using R410A is 50 percentage points higher than that using R407C and the pressure ratio of R410A is 10% less than that of R407C. COP using R410A equals 96% of that using R22 and the volumetric refrigerating capacity equals 147% of that using R22. COP using R407C is equal to 93% of that using R22 and the volumetric refrigerating capacity is equal to 97% of that using R22. R410A is a more appropriate alternative to R22 than R407C in a refrigeration-type compressed-air dryer.