Identification of Lightning Disturbance in UHVDC Transmission Lines Using Correlation Degree Based on Short Time Window Data

Article Preview

Abstract:

In this paper, the simulation of ±800kV UHVDC transmission line in which fault lightning stroke and non-fault lightning stroke, line short circuit occur shows: because there is fault current lumped parameter access to earth during the fault lightning stroke or ground fault, the voltage waveform decrease suddenly and cross repeatedly the zero line in 5ms time window;There is no fault current accessing to earth during non-fault lighting stroke, the disturbance caused by lightning is too less than value of the pole voltage. The voltage waveform comes from the protect position change up and down around the direct voltage line and decays to the pole voltage line in the 5ms time window at last. In the case of the fault lightning or ground fault non-lightning, the correlation degree of transient component and pole voltage line in the time window is little. On the contrary, it is large during the non-fault lighting. Above this, the correlation degree is calculated using 5ms samples. This kind of algorithm can resist random noise effectively,calculating speed is very fast. Many PSCAD simulations show that the algorithm can identify lighting disturbance correctly.

You might also be interested in these eBooks

Info:

Periodical:

Advanced Materials Research (Volumes 433-440)

Pages:

3787-3791

Citation:

Online since:

January 2012

Export:

Price:

Permissions CCC:

Permissions PLS:

Сopyright:

© 2012 Trans Tech Publications Ltd. All Rights Reserved

Share:

Citation:

[1] Zhang Baohui, Hao Zhiguo. Development of relay protection for smart grid(1)--new principal of fault distinction[J]. electric power automation equipment, 2010, 30(1): 1-6.

Google Scholar

[2] DONG Xingli, GE Yaozhong, DONG Xinzhou. Effect of lighting on protection based on travelling waves[J]. Proceedings of the CSEE, 2002, 22(9): 74-05.

Google Scholar

[3] DUAN Jiandong, REN Jinfeng, ZHANG Baohui, LUO Sibei Study of transient approach of discriminating lightning disturbance in ultra-high-speed protection 2006, 26(23): 07-07.

Google Scholar

[4] SI Dajun, SHU Hongchun, CHEN Xueyun, YU Jilai Study on characteristics and identification of transiedts on transmission lines caused by lighting stroke Proceedings of the CSEE, 2005, 25(7): 64-06.

Google Scholar

[5] HANMinxiao, DINGHui, CHENniuyu. Electromabnetic transient modeling of HVDC system[J]. Proceedings of the CSU-EPSA. 2008, 20(4): 7-11.

Google Scholar

[6] China south grid company. Study on transporting power of UHVDC technology[M]. Beijing:China power press, 2006:209.

Google Scholar

[7] Gatta F M, Geri A, Lauria S. Backflashover simulation of HV transmission lines with concentrated tower ground[J]. Electric Power System Rearch, 2005, 73(3): 373-381.

DOI: 10.1016/j.epsr.2004.08.011

Google Scholar

[8] CHEN Qian Operation and control of VSC based multi-terminal HVDC system [D]. Nanjing: Dongnan University. (2004).

Google Scholar

[9] Li Aimin, Cai Zexiang, Ren Dayong. Analysis on the dynamic performance characteristics of HVDC control and protection for the HVDC line fauls[J]. automation of electric power system, 2009, 33(11): 72-75.

Google Scholar