Structural Response and Pounding of Andalas University Hospital Building Using New Indonesian Seismic Code SNI 1726-2012
Abstract:
Keywords: Earthquake, Internal Forces, Displacement, Response Spectrum Analysis, Time History Analysis, PoundingAbstract. Teaching Hospital is an educational facilitiy for students in the Faculty of Medicine and also as a health services for the general public. The hospital building must be built in accordance with earthquake-safe building standards, so that buildings are not damaged in an earthquake. Andalas University Hospital was built at Padang in 2014 which was designed using Indonesian Seismic Code SNI 03-1726-2002 with quakes zone 6. Since 2012, a new Seismic Code, SNI 1726-2012, was issued and all the buildings should be designed by using the new code. Therefore, the authors are interested in analyzing the structural response of the hospital building by using new seismic code SNI 1726-2012. The results, then, were compared with the responses of the structure which calculated by using SNI 03-1726-2002.The results of analysis show that the structural responses in the internal forces and displacement by using SNI 1726-2012 was higher than those using SNI 03-1726-2002. In this study, an analysis of potential Pounding was also conducted by using dynamic analysis Time History method. The analytical result shows that there is no pounding between adjacent buildings at Andalas University Hospital Buildings.